IEC 類別
|
C1
|
|
C2
|
|
C3
|
|
D1
|
額定電壓 UN
|
12 V DC
|
最大持續(xù)工作電壓UC
|
15 V DC
|
|
10 V AC
|
額定電流
|
600 mA (56 °C)
|
UC時,有效工作電流IC
|
≤ 100 ?A
|
殘流IPE
|
≤ 1 ?A
|
標稱放電電流In (8/20) ?s(線芯-線芯)
|
5 kA
|
標稱放電電流In (8/20) ?s(線芯-地)
|
5 kA
|
標稱放電電流In (8/20) ?s(線芯-信號接地)
|
5 kA
|
脈沖放電電流Iimp (10/350) ?s(線芯-線芯)
|
0.5 kA
|
脈沖放電電流Iimp (10/350) ?s(線芯-地)
|
0.5 kA
|
脈沖放電電流Iimp(10/350) ?s(線-信號地)
|
0.5 kA
|
總放電電流Itotal (8/20) ?s
|
10 kA
|
電壓保護水平Up(線芯-線芯)
|
≤ 220 V (C1 - 1 kV/500 A)
|
|
≤ 350 V (C2 - 10 kV / 5 kA)
|
|
≤ 25 V (C3 - 25 A)
|
|
≤ 35 V (C3 - 100 A)
|
電壓保護水平Up(線芯-地)
|
≤ 900 V (C1 - 1 kV/500 A)
|
|
≤ 1.05 kV (C2 - 10 kV / 5 kA)
|
|
≤ 1.3 kV (C3 - 25 A)
|
|
≤ 1.4 kV (C3 - 100 A)
|
電壓保護水平Up(線-信號地)
|
≤ 750 V (C1 - 1 kV/500 A)
|
|
≤ 750 V (C2 - 10 kV / 5 kA)
|
|
≤ 700 V (C3 - 25 A)
|
|
≤ 750 V (C3 - 100 A)
|
電壓防護等級Up靜態(tài)(線芯-線芯)
|
≤ 30 V (C1 - 1 kV/500 A)
|
|
≤ 85 V (C2 - 10 kV / 5 kA)
|
電壓防護等級Up靜態(tài)(線芯-接地)
|
≤ 900 V (C1 - 1 kV/500 A)
|
|
≤ 1.05 kV (C2 - 10 kV / 5 kA)
|
電壓保護水平Up靜態(tài)(線-信號地)
|
≤ 750 V (C1 - 1 kV/500 A)
|
|
≤ 750 V (C2 - 10 kV / 5 kA)
|
響應時間tA(線芯-線芯)
|
≤ 1 ns
|
響應時間tA(線-信號地)
|
≤ 100 ns
|
響應時間tA(線芯-地)
|
≤ 100 ns
|
輸入衰減aE,對稱
|
典型值 0.3 dB (≤ 130 kHz / 150 Ω)
|
截止頻率fg(3dB),150 Ω 對稱系統(tǒng)
|
典型值 420 kHz
|
電容(線芯-線芯)
|
典型值 5.2 nF
|
每條路徑的電阻
|
1.65 Ω ±20 %
|
需要的最大備用保險絲
|
630 mA (FF)
|
電涌電流電阻(導線-導線)
|
C1 - 1 kV / 500 A
|
|
C2 - 10 kV / 5 kA
|
|
C3 - 100 A
|
電涌電流電阻(導線-接地)
|
C1 - 1 kV / 500 A
|
|
C2 - 10 kV / 5 kA
|
|
C3 - 100 A
|
|
D1 - 500 A
|
電涌電流承載能力(線-信號地)
|
C1 - 1 kV / 500 A
|
|
C2 - 10 kV / 5 kA
|
|
C3 - 100 A
|
|
D1 - 500 A
|
脈沖復位時間(導線-導線)
|
≤ 700 ms
|
脈沖復位時間(導線-接地)
|
≤ 30 ms
|
脈沖復位時間(線-信號地)
|
≤ 1500 ms
|